COMMITTEE SUBSTITUTE
FOR ORDINANCE NO. 100346
Amending Chapter 18, Code of Ordinances, by repealing
Article III, Section 18-57, Adoption of International Residential Code (2006);
amendments, and enacting in lieu thereof a new article and section of like
number and subject matter, to establish standards to make dwelling units
resistant to unlawful entry.
BE IT ORDAINED BY THE COUNCIL OF KANSAS CITY:
Section 1. That Chapter 18, Code of Ordinances
of the City of Kansas City, Missouri, is hereby amended by repealing Article
III, Section 18-57, Adoption of International Residential Code (2006);
amendments, and enacting in lieu thereof a new article and section of like
number and subject matter, to read as follows:
ARTICLE
III. RESIDENTIAL CODE FOR ONE- AND TWO-FAMILY DWELLINGS
Sec. 18-57. Adoption of
International Residential Code (2006); amendments.
The International
Residential Code (2006), promulgated by the International Code Council, is
adopted and incorporated in this article by reference as if fully set forth,
except as it is amended by the following provisions of this section.
Provisions of this article are in addition to the provisions of the International
Residential Code. The following provisions coinciding with provisions of
the International Residential Code supercede, or delete, when indicated,
the corresponding provisions of the International Residential Code:
All references
within the model codes to any building, electrical, gas, mechanical, plumbing,
sewage disposal, elevator, energy conservation, or existing building code shall
be construed to be a reference to the respective building, electrical, gas,
mechanical, plumbing, sewage disposal, elevator, energy conservation, or
existing building code specifically adopted by reference in articles II through
XIV of this code.
Part I, Chapter I,
Administrative, is deleted. See article I of this chapter.
For temporary erosion and
sediment control requirements see section 3307.2 of Article II of this chapter.
In Section R202, the
following definitions have been revised or added:
BRACED WALL
LINE, CONTINUOUSLY-SHEATHED. A braced wall line with structural sheathing
applied to all sheathable surfaces including the areas above and below
openings.
TOWNHOUSE. An attached single-family dwelling unit, in which each
unit extends from foundation to roof and with open space on at least two sides,
constructed:
In a group of three or more attached units; or,
In a group of two units where a property line exists
between the units on the underlying parcels.
WATER SERVICE
PIPE. The pipe from the water main or other source of potable water supply
to the first shut-off valve downstream of all of the following (as
applicable): 1. the point of entrance into the building; 2. the water meter;
or 3. the service backflow prevention device.
Table R301.2 (1)
CLIMATIC AND
GEOGRAPHIC DESIGN CRITERIA
GROUND
SNOW
LOAD
|
WIND
SPEEDd
(mph)
|
SEISMIC
DESIGN
CATEGORYf
|
SUBJECT TO DAMAGE FROM
|
Weatheringa
|
Frost
line
depthb
|
Termitec
|
|
20 psf
|
90
|
A
|
Severe
|
36”
|
Moderate
To
Heavy
|
|
WINTER
DESIGN
TEMPe
|
ICE BARRIER
UNDERLAYMENT
REQUIREDh
|
FLOOD
HAZARDSg
|
AIR
FREEZING
INDEXi
|
MEAN
ANNUAL
TEMPj
|
6°F
|
No
|
See
Ordinance
Chapter 28
|
1000° F-days
|
53° F
|
(See 2006 International
Residential Code for footnotes.)
Table
R301.5 Minimum Uniformly Distributed Live Loads – Amend footnotes
b, d and h to read as follows:
b. ‘Attics without storage’ are those where
any one of the following conditions apply:
(i) the maximum clear height between joist and rafter is
less than 42 inches, or where there are not two or more adjacent trusses with
the same web configuration capable of containing a rectangle 42 inches high by
2 feet wide, or greater, located within the plane of the truss; or,
(ii) there is no attic access greater than the minimum
access opening required by Section R807; or,
(iii) the ceiling joist or truss bottom chord pitch is
greater than 2:12.
For ‘attics without storage,’ this live load
need not be assumed to act concurrently with any other live load requirements.
g. For ‘attics with limited storage’ and
constructed with trusses, this live load need be applied only to those portions
of the bottom chord where there are two or more adjacent trusses with the same
web configuration capable of containing a rectangle 42 inches high or greater
by 2 feet wide or greater, located within the plane of the truss. The rectangle
shall fit between the top of the bottom chord and the bottom of any other truss
member.
h. Attic spaces meeting the minimum
requirements of Sections R304 and R305 and served by a fixed stair or a doorway
shall be designed to support the minimum live load specified for sleeping
rooms.
Table R302.1
EXTERIOR WALLS
Add or amend the following rows from Table R302.1 as
follows (remainder of Table unchanged):
EXTERIOR WALL ELEMENT
|
MINIMUM
FIRE-RESISTANCE RATING
|
MINIMUM FIRE SEPARATION DISTANCE
|
Projections
|
Not Allowed
|
N/A
|
< 2 feet
|
(Fire-resistance rated)
|
1 hour on the underside
|
2 feet
|
(Not fire-resistance rated
|
0 hours
|
5 feet
|
R308.4
Hazardous Locations (Glazing)
Exception
5. Glazing in Section R308.4, Item 7, when a
protective bar is installed on the accessible side(s) of the glazing 36 inches
± 2 inches (914 mm ± 51 mm) above the floor. The bar shall be capable of
withstanding a horizontal load of 50 pounds per linear foot (730 N/m) without
contacting the glass and be a minimum of 11/2 inches (38 mm) in height.
Exception 9.
Safety glazing in Section R308.4, Items 10 and 11, is not required where:
9.1. The side of a stairway, landing or
ramp has a guardrail or solid wall complying with Section R312 and Table
R301.5; and
9.2. The plane of the glass is more than 18 inches (457
mm) from the railing or wall.
R310.1,
Exception 2. Except
where sleeping rooms are created, emergency rescue openings need not be
increased in existing basements undergoing interior finish renovation.
R319.3
Fasteners, Exception 3.
3. Borate-treated wood (limited to
interior use only).
R325
Moved Structures. Structures
moved into or within the jurisdiction shall comply with the provisions of this
code for new structures.
R326 Physical Security
R326.1 Purpose. The
purpose of this Section is to establish minimum standards that incorporate
physical security to make dwelling units resistant to unlawful entry.
R326.1.1
Scope. This section shall apply to all dwelling unit exterior doors.
Exceptions:
1. Vehicle
access doors.
2. Storm or
screen doors.
R326.2 Doors. Doors shall
comply with Sections R326.2.1 through R326.2.3.
R326.2.1
Wood doors. Wood doors shall be of solid core construction such as
high-density particleboard, solid wood, or wood block core with a minimum nominal
thickness of one and three-fourths inches (1 3/4") at any point.
Exception:
Solid wood panels shall be a minimum of one inch (1”) thick. The tapered
portion of the panel that inserts into the groove of the door shall be a
minimum of one-quarter inch (¼”) thick. The groove shall be a dado groove or
applied molding construction. The groove shall be a minimum of one-half inch
(½”) in depth.
R326.2.2
Steel doors. Steel doors shall be a minimum nominal thickness of one and
three-fourths inches (1 ¾”) and shall have a minimal skin thickness of 24
gauge.
R326.2.3
Fiberglass doors. Fiberglass doors shall be a minimum nominal thickness of
one and three fourths inches (1 ¾”) and shall have a minimum skin thickness of
one-sixteenth inch (1/16").
R326.3 Door frames. Door
frames shall comply with Sections R326.3.1 through R326.3.4 and shall be
installed in accordance with the manufacturer’s installation instructions.
Door frames shall be installed prior to rough-in inspection.
R326.3.1
Wall framing at door openings. Door frames shall be set in openings
constructed with double studs on each side. Doors with sidelights shall have
double stud construction on each side of the door and on each side of the
sidelight(s). Horizontal blocking shall be placed between studs at the door
lock height for three (3) stud spaces on each side of the door opening.
Exception:
Installations provided with alternative reinforcing methods as approved by the
building official where it is determined that such alternative methods are at least
the equivalent of that prescribed with respect to strength and safety.
R326.3.2
Wood frames. Door jambs shall be a minimum nominal thickness of
three fourths inches (¾”) and shall be installed with solid backing in a manner
so no void exists between the strike side of the jamb and the frame opening for
a vertical distance of twelve inches (12") each side of the strike.
Filler material shall consist of solid wood blocking.
Exception:
Installations provided with alternative reinforcing methods as approved by the
building official where it is determined that such alternative methods are at
least the equivalent of that prescribed with respect to strength and safety.
R326.3.3
Steel frames. Steel door frames shall be constructed of 18 gauge or
heavier steel with reinforcement at the hinges and strikes. Steel frames shall
be anchored to the wall in accordance with manufacturer specifications.
R326.3.4
Sliding doors. Sliding door assemblies shall be installed to prevent the
removal of the panels and the glazing from the exterior. Shims or screws shall
be installed in the upper track of doors that slide on the bottom track or
doors shall be provided with equivalent protection as approved by the building
official..
R326.4 Door hardware.
Door hardware shall comply with Sections R326.4.1 through
R326.4.7.
R326.4.1
Hinges. Hinges for swinging doors shall comply with the following:
A.
A minimum of three (3) four inch (4”) hinges shall be installed on each
swinging door.
B.
Each hinge shall be attached to the frame with at least two (2) screws,
not less than three inches (3”) in length and penetrating at least one inch
(1”) into the nearest stud. Solid wood fillers or shims shall be used to
eliminate any space between the wall structure and door frame behind each
hinge.
Exception:
Installations provided with alternative reinforcing methods as approved by the
building official where it is determined that such alternative methods are at
least the equivalent of that prescribed with respect to strength and safety.
C. Hinges for
out-swinging doors shall be equipped with mechanical interlock to preclude the
removal of the door from the exterior.
R326.4.2
Locks. Swinging doors shall be provided with a single-cylinder deadbolt
locking device (keyed on exterior only) with a minimum projection of one inch
(1"). The deadbolt shall penetrate at least three-fourths inch
(3/4") into the strike receiving the projected bolt. The cylinder shall
have a twist-resistant, tapered hardened steel cylinder guard. The cylinder
shall have a minimum of five (5) pin tumblers, shall be connected to the inner
portion of the lock by solid metal connecting screws at least one-fourth inch
(1/4") in diameter and two and one-fourth inches (2-1/4") in length.
The bolt assembly (bolt housing) unit shall be of single piece construction.
All deadbolts shall meet ANSI grade 2 specifications.
Exception:
Doors with integral multi-point locking devices.
R326.4.3
Strike plates. The deadbolt strike plate shall be a minimum of 18 gauge
metal with four offset screw holes. The strike plate shall be attached to the
door jamb with four screws not less than three inches (3") in length, and
penetrating at least one inch (1”) into the nearest stud.
Exception:
Installations provided with alternative reinforcing methods as approved by the
building official where it is determined that such alternative methods are at
least the equivalent of that prescribed with respect to strength and safety.
R326.4.4 Door
edge protector. A metal L-shaped or U-shaped door edge protector shall be
installed around the bolt projection of the deadbolt to protect the door’s
edge.
R326.4.5
Double doors. The inactive leaf of a double swinging door shall be
provided with flush bolts having an engagement of not less than one inch into
the head and threshold of the door frame.
R326.4.6
Sliding doors. All sliding glass doors shall be equipped with a secondary
locking device consisting of a metal pin, a surface mounted bolt assembly, or
other equivalent device as approved by the building official. Where used, metal
pins shall be installed at the intersection of the inner and outer panels of
the inside door and shall not penetrate the frame’s exterior surface.
R326.5 Entry vision and
glazing. All main or front entry doors to dwelling units shall be arranged
so that the occupant has a view of the area immediately outside the door
without opening the door. The view may be provided by a door viewer having a
field of view not less than 180 degrees or through windows or view ports.
R326.6 Exterior Lighting.
In addition to the lighting outlet requirements of Section E3803, exterior
lighting shall be provided in accordance with this section.
R326.6.1
Front and street side exterior lighting. All front and streetside door
entrances shall be protected with a minimum of one lighting outlet providing a
minimum of 60 watt lighting (or energy efficient equivalent).
R326.6.2
Rear exterior lighting. Dwelling units with windows or doors on the rear
of the structure within eight feet (8') of grade or adjacent walking surface
accessible from grade shall be equipped at the rear with a minimum of one
lighting outlet of the flood light type providing a minimum of 65 watt lighting
(or energy efficient equivalent) .
R326.6.3
Lighting protection. Lighting outlets required by this section shall be
located a minimum of eight feet (8’) above grade or adjacent walking surface
accessible from grade, or shall be of a type manufactured such that the light bulb
is not readily accessible.
R404.5 Retaining Walls.
Retaining walls that are not laterally supported at the top and that retain in
excess of 48 inches (610 mm) of unbalanced fill, that support a surcharge, or are
adjacent to a public right-of-way shall be designed to ensure stability against
overturning, sliding, excessive foundation pressure and water uplift. Retaining
walls shall be designed for a safety factor of 1.5 against lateral sliding and
overturning.
R602.10.5
Continuously-sheathed braced wall line using Method 3 (wood structural panel). Continuously
sheathed braced wall lines using wood structural panels shall comply with this
section. Different bracing methods shall not be permitted within a continuously
sheathed braced wall line. Other bracing methods prescribed by this code shall
be permitted on other braced wall lines on the same story level or on different
story levels of the building.
R602.10.5.1
Continuously-sheathed braced wall line requirements. Continuously-sheathed
braced wall lines shall be in accordance with Figures R602.10.5.3 (1 through 4)
and shall comply with all of the following requirements:
1. Structural
sheathing shall be applied to all exterior sheathable surfaces of a braced wall
line including areas above and below openings.
2. Only
full-height braced wall panels shall be used for calculating the braced wall
amount percentage in accordance with Table R602.10.1.
R602.10.5.2
Braced wall panel length. In a continuously-sheathed wood structural panel
braced wall line, the minimum braced wall panel length shall be permitted to be
in accordance with Table R602.10.5.
R602.10.5.3
Braced wall panel location and corner construction. A braced wall panel
shall be located at each end of a continuously sheathed braced wall line. A
minimum 24-inch wood structural panel corner return shall be provided at both
ends of a continuously-sheathed braced wall line in accordance with Figure
R602.10.5.3(1). In lieu of the corner return, a tie-down device with a minimum
uplift design value of 800 lb shall be fastened to the corner stud and to the
foundation or framing below in accordance with Figure R602.10.5.3(2).
Exception: The
first braced wall panel shall be permitted to begin 12 feet from each end of
the braced wall line provided one of the following is satisfied:
1. A minimum
2-foot-long, full-height wood structural panel is provided at both sides of a
corner constructed in accordance with Figure R602.10.5 at the braced wall line
ends in accordance with Figure R602.10.5.3(3); or,
2. The braced
wall panel closest to the corner shall have a tie-down device with a minimum
uplift design value of 800 lb fastened to the stud at the edge of the braced
wall panel closest to the corner and to the foundation or framing below in
accordance with Figure R602.10.5.3(4).
R602.10.5.4
Braced wall amount percentage. In addition to bracing percentage
adjustments specified elsewhere in this code, the braced wall percentages for
Method 3 from Table 602.10.1 shall be permitted to be multiplied by a factor in
accordance with Table R602.10.5.4.
TABLE R602.10.5.4 ADJUSTMENT
FACTORS TO THE PERCENTAGE OF REQUIRED BRACING PER WALL LINE -- CONTINUOUSLY
SHEATHED a
ADJUSTMENT
BASED ON MAXIMUM WALL CLEAR OPENING HEIGHT:
|
MULTIPLY
PERCENTAGE OF BRACING PER WALL LINE BY:
|
Continuous wood structural panel
sheathing when maximum opening height in wall line does not exceed:
|
85%
of wall height
|
0.9
|
67%
of wall height
|
0.8
|
a. Percentage of bracing for
continuous wood structural panel sheathing shall be based on Method 3
requirements.
TABLE
R602.10.5 LENGTH REQUIREMENTS FOR BRACED WALL PANELS IN
A
CONTINUOUSLY SHEATHED WALL – Amend
Footnote C only:
c. Walls on either side of openings in garages that are
part of a continuously-sheathed braced wall line shall be permitted to be built
in accordance with Section R602.10.6.2 and Figure R602.10.6.2 except
that a single bottom plate shall be permitted and two
anchor bolts shall be placed at 1/3 points. In addition, tie-down devices shall
not be required and the vertical wall segment shall have a maximum 6:1
height-to-width ratio (with height being measured from top of header to the
bottom of the sill plate). Corner returns at the ends of the garage opening
wall shall be a minimum of 2-feet in length and shall be in accordance with
Figure R602.10.5.3(1). This option shall be permitted
for the first story of two-story applications.

FIGURE R602.10.5.3(1) CONTINUOUSLY-SHEATHED BRACED WALL
LINE

FIGURE R602.10.5.3(2) CONTINUOUSLY-SHEATHED BRACED WALL
LINE-WITHOUT CORNER RETURN

FIGURE R602.10.5.3(3) CONTINUOUSLY SHEATHED BRACED WALL
LINE-FIRST BRACED WALL PANEL AWAY FROM END OF WALL LINE WITHOUT TIE DOWN

FIGURE R602.10.5.3(4) CONTINUOUSLY SHEATHED BRACED WALL
LINE – FIRST BRACED WALL PANEL AWAY FROM END OF WALL LINE WITH TIE DOWN
R602.6.1,
Figure R602.6.1 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an
exterior wall or interior load-bearing wall, necessitating cutting, drilling or
notching of the top plate by more than 50 percent of its width, a galvanized
metal tie of not less than 0.054 inch thick (1.37 mm) (16 ga) and 1 1/2 inches
(38 mm) wide shall be fastened across and to the plate at each side of the
opening with not less than eight 10d nails at each side, or equivalent. See Figure
R602.6.1.
Exception:
When the entire side of the wall with
the notch or cut is covered by wood structural panel sheathing.
R613.2 Window Sills is deleted.
R703.6.2, Exception. Plaster
installed per an approved listing or evaluation report.
R801.3 Roof drainage. All
dwellings shall have a controlled method of water disposal from roofs that will
collect and discharge all roof drainage to the ground surface at least 3 feet
(1524 mm) from foundation walls or to an approved drainage system.
R901.2 Restrictive covenants. It
shall be unlawful for any individual or organization to establish or enforce
restrictive covenants which prohibit or effectively prevent the owner of a one-
or two-family dwelling or townhouse from using any types of shingles for roof
covering materials allowed by this code, including wood shingle, wood shake
shingle, composition, slate, tile, clay, or concrete. Nothing in this
ordinance shall prohibit a homes association, if it determines to do so, from
adopting restrictive covenants or otherwise governing the use of such roofing
materials only to the extent of regulating the colors, styles, or dimensions of
roofing materials, or other aesthetic factors. Notwithstanding any existing
procedural provisions governing the time period for consideration of amendments
of restrictive covenants by home associations to the contrary, a home
association, if it determines to do so, may amend their restrictive covenants
to provide for such aesthetic regulations for a period of 180 days from the effective
date of this ordinance. Any such amendments after that 180 day period of time
shall be subject to any procedural requirements set forth in such covenants.
R907.3 Recovering versus
replacement (Reroofing), Condition #4. For asphalt shingles, when the
building is located in an area subject to severe hail exposure according to
Figure R903.5.
N1102.2.6 (Insulation),
Exception. Concrete or masonry basement walls in unfinished basement
areas.
Part V, Chapter 12, Mechanical
Administration, is deleted.
Sections
M2001, M2002, M2003, and G2452 (Boilers) are deleted.
Part VII, Chapter 25, Plumbing
Administration, is deleted.
P2602.1.1. For the
purpose of this section, available means located in a public way or easement
abutting the subject property and within 200 feet of the proposed building.
P2706.2 Standpipes. Standpipes
for automatic clothes washers shall extend a minimum of 30 inches (762 mm) and
a maximum of 48 inches (1219 mm) above the finished floor. The trap for a
clothes washer standpipe shall be installed at a maximum of 12 inches (305 mm)
above the finished floor. Access shall be provided to all standpipe traps and
drains for rodding.
P2706.2.1
Laundry tray connection. A laundry tray waste line is permitted to connect
into a standpipe for the automatic clothes washer drain. The standpipes shall
not be less than 30 inches (762 mm) as measured from the crown weir. The
outlet of the laundry tray shall be a maximum horizontal distance of 30 inches
(762 mm) from the standpipe trap.
P2901.2. References in
this code to water service piping shall apply only to water service piping
connected to a private source of water supply. All water service piping
connected to the public water supply is under the jurisdiction of the
Department of Water Services.
P2902.5.3
Lawn irrigation systems. The potable
water supply to lawn irrigation systems shall be protected against backflow by
a double check valve assembly or a reduced pressure principle backflow
preventer. Where chemicals are introduced into the system, the potable water
supply shall be protected against backflow by a reduced pressure principle
backflow preventer.
P2903.8.2
Minimum size.
The minimum size of individual distribution lines shall be ½” (12.7 mm).
Certain fixtures such as one-piece water closets and whirlpool bathtubs shall
require a larger size where specified by the manufacturer. If a water heater
is fed from one end of a cold water manifold, the manifold shall be one size
larger than the water heater feed.
Table
P2904.4.1, Water Service Pipe. Delete “Polybutylene (PB) plastic pipe
and tubing.”
Table
P2904.5, Water Distribution Pipe. Delete “pipe and” from “Polybutylene
(PB) plastic pipe and tubing.”
P2904.5.1
Under concrete slabs.
Inaccessible water distribution piping under slabs shall be copper water tube
minimum Type L, brass, ductile iron pressure pipe, cross-linked
polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX), chlorinated
polyvinyl chloride (CPVC) or crosslinked polyethylene (PEX) plastic pipe or
tubing – all to be installed with approved fittings or bends. The minimum pressure
rating for plastic pipe or tubing installed under slabs shall be 100 psi at 180
degrees F (689 kPa at 82 degrees C).
Table
P3002.2 Building Sewer Pipe. Delete “SDR 41” and “SDR 35” from “Polyvinyl
chloride (PVC) plastic pipe.”
P3008.1,
Exception.
The backwater valve is not required unless the structure is connected to a
combination storm/sanitary sewer, or the structure or the next downstream sewer
manhole is located in the regulatory floodplain.
P3105.4
Floor drain. A floor drain (where used as such) need not be vented,
provided it is within 25 feet of a three-inch stack or horizontal drain which
has at least a three-inch-diameter vent extension through the roof.
P3114.3 Where permitted.
Vents may terminate to an air admittance valve under the following conditions:
(1)
For
sinks located where there is no wall accessible from the sink location (eg
island sinks); or where access to the vent system would require notching or
boring of studs in excess of the limitations of section R602.6.
(2) In existing
construction, where the existing vent system is not accessible to the fixture
location without the removal of finish materials or other existing
construction.
E3802.12
Arc-fault protection of bedroom outlets. All
branch circuits that supply 120-volt, single-phase, 15- and 20-ampere outlets
installed in bedrooms shall be protected by a combination type or branch/feeder
type arc-fault circuit interrupter installed to provide protection of the
entire branch circuit.
Exception: The
location of the arc-fault circuit interrupter shall be permitted to be at other
than the origination of the branch circuit provided that:
1. The arc-fault circuit interrupter is installed within
6 feet (1.8 m) of the branch circuit overcurrent device as measured along the
branch circuit conductors; and,
2. The circuit conductors between the branch circuit
overcurrent device and the arc-fault circuit interrupter are installed in a
metal raceway or a cable with a metallic sheath.
Part X, Appendices: The
following appendix chapters are hereby adopted:
Appendix G,
Swimming Pool Enclosures.
Section AG101. Swimming pools
shall be completely enclosed by a barrier at least 4 feet (1290 mm) in height.
Openings in the barrier shall not permit the passage of a 4-inch (102 mm)
diameter sphere. Gates in the barrier shall be self-closing and self-latching;
and shall be maintained locked when the pool is not tended by a responsible
person.
Sections AG103 through AG107 are
deleted.
Appendix I, Private
Sewage Disposal. [See Article VIII of this chapter.]
Secs. 18-58—18-73. Reserved.
_____________________________________________
Approved
as to form and legality:
___________________________________
M.
Margaret Sheahan Moran
Assistant City Attorney